Product details

The Santak SPU series 5kVA Power-Specific UPS is built on over 30 years of industry expertise, strictly adhering to DL/T5491-2014 and DL/T1074-2019 power industry standards. The device features a dual-isolation design, supports 220V±25% AC input and DC220V/110V input, with output voltage accuracy reaching AC220V±1%, and operates stably in wide-temperature environments from -25℃ to 55℃. Its unique design effectively meets the specific DC bus access needs of the power industry, directly connecting to power plant DC systems via reverse diodes, saving 60% on battery investment and reducing maintenance costs.Equipped with an intelligent protection system including overload bypass switching, short-circuit current limiting, and low-battery automatic shutdown, it ensures uninterrupted power supply for critical equipment like DCS control systems and DEH electro-hydraulic devices under complex conditions such as surge impacts and nonlinear loads. With overall efficiency ≥83% and electromagnetic compatibility certification, it meets 3-20kVA power protection needs for scenarios like power plant booster stations and grid company substations.

Product Features

  • Dual-isolation design supports 220V±25% AC input and DC220V/110V DC input, achieving physical isolation protection between grid and load
  • Output voltage accuracy reaches AC220V±1%, overall efficiency ≥83%, compliant with DL/T5491-2014 and DL/T1074-2019 power industry standards
  • Built-in reverse diode technology enables direct connection to power plant DC bus systems, reducing 60% battery configuration requirements and maintenance costs
  • Equipped with wide-temperature operation capability (-25℃ to 55℃), adaptable to harsh industrial environments like high dust and strong corrosion in power plants
  • Integrated smart protection system includes overload bypass, short-circuit current limiting, and low-voltage battery shutdown to ensure continuous power supply under extreme conditions

Application Scenarios

  • Uninterrupted power supply for core equipment of power plant DCS distributed control systems
  • Stable power support for substation relay protection devices and automated monitoring systems
  • Emergency power supply for critical process equipment like DEH electro-hydraulic regulation systems in power plants
  • 3-20kVA power assurance requirements for scenarios like grid company booster stations and converter stations
  • Power purification and protection for precision instruments in high-interference industrial environments such as petrochemical and metallurgical industries

Product Parameters

  • Model:Power-specific UPS SPU 5kVA
  • Rated Capacity:5kVA
  • DC Source (DC220V):Y
  • DC Source (DC110V):Y
  • Input AC Single Phase (1P):Y(1P2W)
  • Input Voltage:220V±25%
  • Input AC Three Phase (3P):Y (3P4W)
  • Input Voltage:380V±25%
  • Input Frequency:50Hz/60Hz ±10%
  • Input DC Voltage and Range:DC220V (Rated) DC180V~DC270V DC110V (Rated) DC90~DC135V
  • Output Voltage and Accuracy:AC220±1% (1P2W)
  • Output Frequency:50Hz/60Hz ±0.1%
  • Output Waveform Distortion Rate:<3% (Linear Load), <5% (Non-linear Load)
  • Output Overload Capacity:<=100% Continuous Load 100%~120% 10 Minutes Transfer to Bypass 120%~150%, 60 Seconds Transfer to Bypass ≥150%, 1 Second Transfer to Bypass
  • Output Power Factor:0.8
  • Output Crest Factor:0.125694444
  • Output Efficiency:≥83%
  • Protection Function Battery:Battery Low Voltage Auto Shutdown, Circuit Breaker Protection
  • Protection Function Overload Capacity:Transfer to bypass after overload, automatically recover after load reduction
  • Protection Function Short Circuit:Current limit auto shutdown, fuse and circuit breaker protection
  • Protection Function Fault:Fault or internal overtemperature, automatically transfer to bypass and alarm
  • Protection Function Frequency:50Hz/60Hz ±10%
  • Protection Function EMI/EMC:DL/T 1074-2019 BG/T 7260.2-2009
Loading...