Santak C2K-M PLUS 2 standby UPS power supply 2kVA/1600W is suitable for the power industry and rail transit industry
Santak UPS C2K-M PLUS 2 is specifically designed for the power and rail transit industries, featuring industrial-grade protection technology to adapt to extreme temperatures, high altitudes, and harsh grid environments, providing stable power supply for core equipment such as fan systems and converters, with a 3-year full-machine warranty to meet unattended requirements.
Buy Now
- WeChat:13775032303
- Email:powercube@foxmail.com
Product details
Santak C2K-M PLUS 2 industrial-grade UPS power supply is developed for harsh scenarios like wind power and rail transit, with built-in redundant design and wide temperature adaptability, capable of stable operation in environments ranging from -25℃ to 60℃ and supporting applications at altitudes up to 4000 meters. Its key components adopt triple-protection coating technology, effectively resisting moisture, salt spray, and mold erosion, ensuring long-term reliability in high-dust wind farm and unattended scenarios.The product complies with the "Application Requirements for Uninterruptible Power Supply in Wind Turbines," featuring an input voltage range of 115-300VAC to address grid fluctuations and voltage drops, ensuring continuous operation of pitch systems and main control units during grid failures, meeting national low-voltage ride-through standards. The unit comes standard with an RS232 communication interface, supporting unattended self-management functions, and can integrate with host monitoring systems via optional dry contact cards. Certified by TLC, CE, and CQC, it offers a 3-year full-machine warranty (including batteries), providing all-weather power protection for scenarios such as new energy generation and outdoor smart terminals.
Product Features
- Industrial-grade wide temperature range design supports stable operation from -25°C to 60°C, adapting to extreme temperatures and harsh high-altitude environments
- PCBA conformal coating process effectively defends against moisture and salt spray corrosion, extending equipment lifespan in high-dust wind farm scenarios
- 115-300VAC ultra-wide input voltage range compatible with poor-quality grids, ensuring continuous operation of core equipment during voltage sags
- Redundant configuration of key components and amplified margin design enhance system reliability, meeting unattended scenario requirements
- 3-year whole-machine warranty including batteries with TLC/CE/CQC multi-certification, reducing maintenance costs in high-altitude areas
Application Scenarios
- Power protection and low-voltage ride-through support for wind turbine main control systems and pitch adjustment devices
- Uninterruptible power supply solutions for rail transit signal control systems and emergency lighting equipment
- Stabilized backup power supply for PV plant inverters and energy storage systems during grid fluctuations
- Power protection for outdoor smart parcel lockers and terminal equipment in salt fog and humid environments
- All-weather stable power supply support for surveying instruments and unmanned delivery equipment in high-altitude regions
Product Parameters
- Model:C2K-M PLUS 2
- Rated Capacity:2kVA/1600W
- Input/output configuration:Input/Output System
- Input configuration:Single Phase
- Rated voltage:230Vac
- Voltage range:115-300VAC
- Frequency:Frequency
- Power factor:0.99
- Bypass Voltage:80VAC×(1±5%)~285VAC×(1±5%)
- Bypass voltage:Default 180VAC×(1±5%)~264VAC×(1±5%)
- Battery Voltage:48VDC
- Internal Battery Capacity:12V 7Ah
- Full Load Backup Time (25℃):4mins
- Battery Charging Current:1A
- Communication Interface:Standard RS232, optional communication card (refer to optional accessories list)
- Output Type:Single Phase
- Rated Voltage:230VAC
- Power Factor:0.8
- Voltage Accuracy:0.01
- Rated Frequency:50/60 Hz
- Overload Capacity @ Utility Mode:105%±5%
- Overload Capacity @ Utility Mode:150%±5%
- Overload capacity @ Utility mode:>200%±5%, transfer to bypass and alarm in 200ms
- Transfer time:0ms (Utility?Battery)
- Transfer Time:<4ms (Utility?Bypass)
- Operating Temperature:-25°C Utility mode with full load startup -25°C~-10°C Utility mode full load operation -10°C~40°C Battery and Utility mode full load 40°C~60°C Load derating as follows: 40°C~55°C output power derates 3% per 1°C increase. 55~60°C 1K(S): 440W 2K(S): 880W 3K(S): 1320W
- Humidity:≤2000m no derating, 2000m< altitude ≤4000m load reduces 1% per 100m increase, for applications above 4000m, consult the manufacturer
- Altitude:Seismic resistance, high/low temperature, salt spray, vibration, altitude, EMC
- Certification:TLC, CE, CQC energy-saving
- Dimensions (W×D×H, mm):190*393*328
- Net Weight (kg):18.3
- Packaging Dimensions (WxDxH mm):325*493*458
- Gross Weight (kg):20.6